Electro-magnetic Emergency Shut-off Valve For Gas

  • Electro-magnetic Emergency Shut-off Valve For Gas
  • Electro-magnetic Emergency Shut-off Valve For Gas
  • Electro-magnetic Emergency Shut-off Valve For Gas
Electro-magnetic Emergency Shut-off Valve For Gas

The Emergency Shutoff Gas Valve(including Residential class and Commercial class ) is a series of Industrial gas emergency shut off valves, specially designed as gas pipe breakers for emergency use. They can be connected with gas leak detection sensors, fire alarm circuits or other intelligent sensor modules so that on site or remote shutdown
on gas supply (manually or automatically) is possible, therefore ensuring safe gas usage.

The gas valve that is automatically(Pulse discharge,driving voltage:≤DC24V times:≤1S) closed by the safety control system or by an emergency device.

ELECTRO-MAGNETIC EMERGENCY SHUT-OFF

VALVE FOR GAS


1The Residential Class

Gas Valve

1.1 The Residential Valve is a series of residential gas emergency shut off valves,specially designed as gas pipe breakers for emergency use. They can be connected with gas leak detection sensors, fire alarm circuits or other intelligent sensor modules so that on site or remote shutdown of the gas supply (manually or automatically) is possible, therefore ensuring safe gas usage.

1.2 The valve features an auto-close when a strong vibration (e.g. earthquake) is detected.

1.3 After auto-closing, manual operation is required to turn on the valve. This feature meets safety regulations in the event of an accident.

1.4 Characteristic:

Actuator is covered with molding resin for explosion-proofing:

 

No static electricity caused sparks.

Safe to be installed on flammable gas pipelines - valve will not enhance fire conditions.

Status:

The gas valve that is automatically(Leakage Detector Pulse discharge, time≤1S) closed by the safety control system or by an emergency device. The valve can only be opened manually when environmental safety is confirmed.

Closing modes:

 

1000uf capacitor pulse discharge to close or Manual close.

Open modes:

 

Manually open. This feature meets the Safety regulations in the event of an accident.

Keep mode:

 

It remains open or closed without power (dual stable states).

Closing time:

≤1 Second.

Shut off on strong vibration (earthquake):

 

Automatically closes valves under strong vibration - vibration sensitivity can be adjusted.

Reliable sealing:

 

A Precision process is used to guarantee the valve is securely sealed; NBR/FKM rubber to ensure long life cycle - typically 10 years.

Reliable operation:

 

Operating parts have been tested over 5000 times without failure.

 1.5 Installation

Electro-Magnetic Valve

2.The Commercial Class

Residential shutoff ValveGas Valve

2.1The Commercial Valve is a series of Industrial gas emergency shut off valves, specially designed as gas pipe breakers for emergency use. They can be connected with gas leak detection sensors, fire alarm circuits or other intelligent sensor modules so that on site or remote shutdown on gas supply (manually or automatically) is possible, therefore ensuring safe gas usage.

2.2The valve features an auto-close when strong vibration or earthquake is detected.

2.3After closure, manual operation is required to turn on the valve. This feature meets safety regulations in the event of an accident.

2.4.1The valve is designed with double structure of mechanical lock and permanent magnet lock.

2.4.2 When the valve is in open state, the spring force is overcome by mechanical lock structure, and the spring is locked in compressed state. The trigger structure of mechanical lock is fixed in open position by permanent magnet lock structure.

2.4.3 When the valve receives the shut-off signal, the discharge module will output pulse current to the electromagnetic coil in permanent magnet lock structure. The instantaneous magnetic force generated by the impulse current will unlock the permanent magnet lock structure, and the trigger structure will run to the closed position.

2.4.4 When the trigger structure reaches the closed position, the mechanical lock will be unlocked, and the valve will be closed by the spring force.

Item

Parameter

Sealing material

NBR/FKM

Valve body material

Casting aluminium alloy(ZL101A)、WCB

Valve closing mode

1、Passive manual closing valve;2、DC12V pulse drive(times≤1S)

Status

The gas valve that is automatically(Leakage Detector Pulse discharge, time≤1S) closed by the safety control system or by an emergency device. The valve can only be opened manually when environmental safety is confirmed.

Action reliability

More than 3000 times

Operational life span

10years

Standard

QB/0001-2018、GB3836.1-2010、GB3836.9-2014、CJ/T394-2018

Maximum working pressure

DN≤20mm:0.02MPa/0.10MPa/0.20MPa

25mm≤DN≤400mm:0.1MPa/0.4MPa/0.6MPa

Ambient temperature

-10℃~+50℃

Place of use

Zone 1, zone 2 in explosive gas environment

Explosion proof mark

Ex mbⅡB T6 Gb

Levels of protection

IP54/IP65(Require cover),

Steel pipe or casing connection at cable-exit position to form a sealed environment

Attended mode

Thread/Flange connection (PN16)

Gas source type

Natural gas, liquefied petroleum gas and artificial gas

Cable length

0.45M/Customer customization

 2.5 Installation

Electro-Magnetic Valve


Get the latest price? We'll respond as soon as possible(within 12 hours)

Privacy policy

close left right